Team Members
a. Angad Bajwa-107118014
b. Mandar Burande-107118056
c. Aditya Pethkar-107118072
Date and time of this submission : 2020-04-14 19:57:35.349101
Inductance per phase per km in H/km : 7.449578E-04 H/km
Capacitance per phase per km in F/km : 1.542961E-08 F/km
Inductive Reactance of the line in Ohm : 37.446 Ohm
Capacitive Reactance of the line in Ohm : 1289.363 Ohm
Charging current drawn for the sending end substation :61.302 A
ABCD Parameters
Nominal Pi Model Medium Transmission Line
A= (0.9854790017117532+0.018613848436635397j)
B= (48+37.445664189680045j) Ohm
C= (-7.218236533792375e-06+0.0007699459419163484j) mho
D= (0.9854790017117532+0.018613848436635397j)
Sending end Voltage :142.026 kV
Sending end Current :148.760 A
Voltage Regulation : 9.161 %
Power Loss :2.747 MW
Transmission Efficiency :91.611 %
Sending End Circle :
a. Centre : (-87.08218372235872+65.32696976971434j)
b. Radius : 102.650
Receiving End Circle :
a. Centre : (-75.22143231010746-56.42931796731364j)
b. Radius : 102.650